Explosion-proof electrical site operation requirements

Explosion-proof safety involves the safety of life and property. On the basis of the explosion-proof products reaching the national standard GB3836-2010, it also requires the operators to master the correct operating knowledge so as to ensure the production safety. The practical operation personnel of explosion-proof equipment must pay attention to many problems in actual operation. Because the operators are working in flammable and explosive environments, if they are operated improperly, it is easy to cause fault problems. Therefore, technical requirements for operators are relatively high. Hualong explosion-proof technical staff has prepared professional operating technical requirements for explosion-proof electrical equipment for this purpose, for use by manufacturers who use explosion-proof products.
Section 1 Explosion Proof Inspection Operation Specifications
First, job requirements
1. Must pass professional training exams, hold certificates, and work independently. Apprentice workers may not work alone in explosion-proof inspections.
2. Must be familiar with "GB3836-2010" related content, "standards" and electrical equipment explosion-proof standards of the relevant provisions.
3. Be familiar with the power supply system and electrical equipment performance within the scope of work. Understand the type, quantity, and distribution of electrical equipment in the area under inspection. .
Second, safety regulations
1. You must not drink alcohol before going to work, and you must not do anything unrelated to your job and abide by relevant rules and regulations.
2. When a power failure is required to check the equipment, the power transmission system must be strictly implemented. The gas concentration of 1% or less is permitted to open the flameproof enclosure, which can be checked after the experience of electricity and discharge.
3. When the problems detected cannot be dealt with on the spot, the relevant units may be notified to take temporary safety measures, and the equipment that has lost the explosion may not be allowed to transmit power.
4. The unreasonable device for relay protection setting, notify the relevant personnel, and re-adjust.
Third, operation preparation
1. Check the tools, meters, parts, and insulation materials for inspection. Check whether the electroscope is in good condition.
2. Before the blackout inspection, contact the relevant department (district team) in advance. Fourth, normal operation
1. Pre-well inspection of electrical equipment:
(1) The electrical equipment used in the well must be subjected to a detailed inspection of the explosion-proof parts such as the roughness of the flameproof joint surface, gaps, and wiring lead-in devices. The explosion-proof performance must meet the requirements of the explosion-proof standard, and it is forbidden to enter the well with the detonation equipment.
(2) Explosion-proof electrical equipment Before man wells, they should check their "product certification", "explosion-proof certificate", "and safety performance.
(3) Manhole equipment inspection records must be filled in. Qualified equipment can be issued with a manhole certificate.
2. Inspection of underground electrical equipment:
(1) Explosion-proof inspectors shall check with the person in charge or maintenance personnel in the area when inspecting electrical equipment downhole.
(2) Whether the surrounding environment of the equipment is clean and there is no obstruction to the safe operation and maintenance of the equipment.
(3) Whether there is a good ventilation and cooling conditions, the shell has no defects.
(4) Whether the installation is firm and reliable, with or without skew and vibration.
(5) The equipment is in good condition and meets the explosion-proof performance and requirements.
1 Power supply cable, control line and signal line cable wiring specifications, leading to the introduction of a good seal, do not use the bell mouth to apply sealing plate tightly closed, no explosion phenomenon;
2 whether there is abnormal sound, overheat, odor;
3 The control part, locking cover, signal display are normal and effective;
4 Grounding (connected to zero) should be standardized, firm, and free of rust.
(6) After completing the inspection, fill in the inspection card or inspection record. When the explosion or major problem is discovered during the inspection, the unit to be inspected must be ordered to handle it on the spot. The inspector shall supervise on the spot until he is finished. Fifth, finishing work
Explosion-proof inspectors shall report the inspection results and handling opinions to the competent personnel, fill in the inspection report form, and send it to the relevant unit within a time limit for settlement.
Zhengzhou Hualong explosion-proof professional distribution box explosion, explosion-proof lamps, explosion-proof inverter, explosion-proof control cabinet, explosion-proof instrument, explosion-proof pipe fittings, etc., are widely used in major oil fields at home and abroad, sea oil, petrochemical, chemical, pharmaceutical, coal, smelting Shipbuilding, shipbuilding, military, textile and other areas as well as national key projects were well received by users.